Slot Diffuser Installation

Posted : admin On 4/7/2022
Slot Diffuser Installation 7,8/10 5164 votes

The purpose of generating this Method Statement is to define the procedure step by step to implement the correct practices for Installation of Grills, Diffusers, Registers & Louvers through the guide line contained herein so as to ensure that the job execution complies with the requirements and serves the intended function to satisfactory level.

  1. Price Linear Slot Diffuser Installation
  2. Price Slot Diffuser Installation Instructions
  3. Linear Slot Diffuser Installation
  4. Texas Buildmart Slot Diffuser Installation

Thanks to the connection possibilities of the slot diffusers it is possible to create continuous diffusers in multiple metres and with different corner angles. The two continuous blade type dampers enable to select the throw direction. Upon demand it is possible to mount sliding type volume regulating dampers at the entries of the slot diffusers. The SCHAKO ceiling slot diffuser type DSCXL ist suitable for room heights from 2.6 m to 4 m for direct installation in plasterboard ceilings or suspended ceilings (pressure ceilings). The ceiling slot diffuser is supplied with 1 slot and is available as single diffuser or in band design.

Following tools and materials shall be arranged before starting the installation works.

  • Portable hand tools.
  • Portable Drilling Machine.
  • Handheld rivet gun
  • Handheld hammer drilling machines.
  • Wooden mallet
  • Spirit Level / Level Threads
  • Step Ladder
  • Scaffolding with platform
  • Ceiling Supply Registers / Grills.
  • Ceiling Exhaust & Return Registers / Grills.
  • Ceiling Supply Diffusers Return / Exhaust Diffusers.
  • Wall Supply Registers / Grills.
  • Wall Exhaust & Return Registers / Grills.
  • Ceiling / Side Wall Linear Slot Diffusers.
Texas buildmart slot diffuser installationLinear

Installation Procedure for Diffusers and Grills:

The following procedure shall be followed for the installation of grills / diffusers:

  • Grills/diffuser shall be submitted for Consultant approval before proceeding with installation.
  • Prior to start of installation, refer to the approved false ceiling drawing related to the area of installation and ensure that required material is available at site as per approved material submittals.
  • Visually inspect the grills / diffuser for any damages.
  • Check whether the grills / diffusers are as specified type as per list provided in approved material submittal.
  • Check whether powder coating quality is O.K. and color is as per specifications.
  • Check horizontal & vertical vanes of grilles and register. There should not be any bend and adequate support should be provided by Manufacturer if grill is long.
  • Check the borders of grills / diffusers for gap free aligned joints.
  • Ensure that the proper clearance is available from civil side before commencement of works.
  • Ensure that the work area is clean and safe for carrying out the installation of grill/diffuser.
  • Ensure that the installation of grills/diffusers are carried out in accordance with manufacturer’s installation recommendations and specification.

INSTALLATION PROCEDURE FOR GRILLS / DIFFUSERS IN CEILING

Installation
  • After competition of the false ceiling work mark location of grill / diffuser location as per approved false ceiling drawing.
  • After grill / diffuser location are confirmed by Site Engineer (HVAC ),opening is to be made in the marked place.
  • After cutting the opening, proper false ceiling support and alignment is to be done.
  • Check level of Gypsum board surface while installing grills and diffusers.
  • Grilles and diffusers should not be directly supported on gypsum surfaces. Proper frame should be provided at the back by the false ceiling contractor.
  • Check grills / diffuser collars are securely fixed to the inside of frame.
  • Check grills / diffuser flexible connection are properly connected with duct and plenum and also both side are clamped with jubilee clamp.
  • Ensure that the damper blades of supply grills and diffusers are properly secured in nylon bushes for rattle free operation.
  • Check whether the items are supplied with specified fixing arrangement counter sunk screw fixing, Concealed with clip / inside screw lever / concealed bracket.
  • Grills / diffuser shall be fixed as per given manufacturer’s arrangement.
  • Ensure alignment and joining clips are provided for all open end slot diffusers for continuous fixing.
  • Check whether each slot is adjustable or not in multi slot diffusers.

INSTALLATION PROCEDURE FOR GRILLS IN WALL

Price linear slot diffuser installation
  • Grill should not be fixed directly on the wall.
  • Wooden frame is to provided for all grill on wall (by Main Contractor ).
  • After first coat painting grill is to be fixed in frames as per manufacturer’s recommendations.
  • Check horizontal & vertical vanes of grills and register. There should not be any bend and adequate support should be provided by Manufacturer if grill is long.

You may also like:

Fields of application

Price Linear Slot Diffuser Installation

The SCHAKO ceiling slot diffuser type DSCXL ist suitable for room heights from 2.6 m to 4 m for direct installation in plasterboard ceilings or suspended ceilings (pressure ceilings). The ceiling slot diffuser is supplied with 1 slot and is available as single diffuser or in band design.

Slot

Function

The large cross section in the SCHAKO DSCXL diffuser allows a high air volume compared to other slot diffusers. Thanks to the stable air jet and high induction, it can be used with temperature differences up to 12K in cooling mode. The pre-pressure generated by the blades ensures that the supply air is distributed equally across the whole length of the diffuser, whether as single diffuser or in band design.
A subsequent change of the air jet outflow direction on site is always possible, since the air deflection blades can be easily adjusted from outside, as usual at SCHAKO.
If an air throw pattern is specified when ordering, it will be preset in factory. The diffuser can be used for supply and return air.

Volumetric flow range

Price Slot Diffuser Installation Instructions

200 - 400 m³/h per metre slot, suitable for VAV systems from 100 - 40%

Linear Slot Diffuser Installation

Please accept marketing-cookies to watch this video.

Texas Buildmart Slot Diffuser Installation

Files